MEWOI168BE-Φ68mm Clamp AC2000A,DC1000A Current sensor probe/meter/tester/pinza

Electricity Testing Instruments manufacturer, Support OEM/ODM, your testing specialist

  • Main Features:: 1,AC/DC current detection 2, Range: AC 0.0A~1000A,DC 0.0A~2000A 3,clamp size:φ68mm,4,Resolution:0.1A
  • Model No.:: MEWOI168BE
  • Name:: MEWOI168BE-Φ68mm Clamp AC2000A,DC1000A Current sensor probe/meter/tester/pinza

Contact Us for QuotationEmail:mewoi@mewoi.comWhatsapp: +8618620373879

Ⅰ.INTRODUCTION

Click to download:  Selection Map

MEWOI168BE Clamp on AC/DC current Sensor is designed for testing AC/DC current with voltage under 600V on-line. Adopt the latest CT technology and digital integrated technology. There is not any metallic conductor outside the clamps, non-contact test to ensure save. It is small in size; high accuracy can connect with multi-meter, oscilloscope, electric power quality analyzer, etc. Widely applied in electricity, communication, meteorology, railway, oilfield, construction, measurement, scientific and research teaching unit, industrial and mining enterprises.

TECHNICAL SPECIFICATION

Function

Measurement of AC current, phase, power energy, power, power factor

Power supply

Zn-Mn dry battery 6F22 9VDC(external power is allowed)

Rated current

15mA

Test mode

Clamp CT, noncontact measurement

Clamp Size

Φ68mm

Range

DC 0.0~2000A; AC 0.0~1000A

Resolution

0.1A AC/DC

Signal output

1mV/1A

Accuracy

±2.0%FS(50Hz/60Hz; 23±2, below 70%RH, keep the wire be in the center of clamp)

Phase Error

≤3°(AC50Hz/60Hz; 23±2)

Zero clearing

Press ZERO key can clear the data, eliminate the effect of geomagnetic field to the measure of AC current
Output connectionStandard connection: Red wire-positive output; Yellow wire-negative output.
Output Wire Length2m

Measured Wire Position

Approximately in the geometric center of the clamp, the errors for deviating the center of the clamp increase 1.5%rdg.

Frequency

AC 45Hz~400Hz

Voltage of circuit

Circuit with the voltage below AC 600V

Voltage of battery

When the voltage of battery is below 7.2V, the LED will be lighted when the voltage is low, indicate to replace the battery.

Dimension

224mm×115mm×43mm

Weight

515g

Working Environment

-15~45;80%rh below

Storage Environment

-10~60;70%rh below

Insulation Strength

AC 3700V/rms. (between core and shell)

Safety Rules

IEC1010-1,IEC1010-2-032,Pollution degree 2,CAT Ⅲ(600V)

Accessory

Sensor:1pc; battery(6F22 9V):1pc

SELECTION GUIDE 1

Clamp on Current Sensor Probe For Terminals Such Mulitimeter&Oscilloscope 

Click "Blue" marked Model No. to View the Spec

ModelRangeResolution
Clamp SizePower Supply&output
Hall effectCurrent induction output,Direct Coil tap Others
MEWOI107BEMEWOI107BE_副本.8.jpg

0mA~60A

 (AC/DC)

1mA  Φ7mm    Power Supply: 9VDC, Output:10mV/A,100mV/A, Accuracy 3%
Suitable for small spaces AC / DC leakage current, low current test.
MEWOI108MEWOI108-1_副本_副本.80.jpg0.0mA~30A (AC)

0.1mA,

Accuracy 0.5% 

Φ8 mm 

Suitable for small spaces AC leakage current, harmonic, phase, Power test
MEWOI130MEWOI130.80.jpg0.000mA~60A (AC), 0.001mA,Accuracy: 1%25*30mm 

Double shielding, anti-jamming capability,suitable for leakage current,small current test.
MEWOI130EMEWOI130.80.jpg0.00A~10A (DC),  0.01A    25*30mm Power supply: 9VDC, output:0~2.5mV/10mA,Accuracy: 3%,Turns ratio:1:800 

Double shielding, anti-jamming capability,suitable for small DC current test.
MEWOI130E2MEWOI130.80.jpg

0.0mA

~100mA

 (DC), 

0.1mA      25*30mm Power supply: 9VDC, output:0~2.5mV/1mA,Accuracy: 3%,Turns ratio:1:800 

Double shielding, anti-jamming capability,suitable for DC leakage current test.
MEWOI130BEMEWOI130BE.0_副本80.jpg0mA~60A (AC/DC)    1mA25*30mmPower supply: 9VDC, output:10mV/A,100mV/A,Accuracy: 2%  
suitable for AC/DC current test
MEWOI135BEMEWOI135BE.80.jpg0.0A~1000A (AC/DC)    0.1A30*35mm     Power supply: 9VDC, output:1mV/1A,Accuracy: 2%   
suitable for AC/DC current test
MEWOI140MEWOI140_副本80.jpg

0.00mA

~300A

 (AC)  

Turn Ratio

1:2400

0.01mA,Accuracy: 1%   35*40mm  

Single shielding, suitable for leakage current, small current test
MEWOI140BMEWOI140_副本80.jpg

0.0A~600A (AC)


Turn Ratio

1:4000


0.1A,

Accuracy: 1% 

35*40mm 

suitable for big current test
MEWOI140CMEWOI140B_副本80.jpg

0.0mA

~100A

 (AC)

Turn Ratio

1:2000

0.1mA,

Accuracy: 1%

35*40mm

suitable for current, harmonic, phase, Power test
MEWOI168MEWOI068-1_副本80.jpg

0.00mA

~1000A 

(AC)       

0.01mA,

Accuracy: 1%       

Φ68mm 

Double shielding, anti-jamming capability,suitable for leakage current, current test
MEWOI168BMEWOI168.80.jpg0.0A~2000A (AC)

0.1A,

Accuracy: 2%

Φ68mm 

suitable for current, harmonic, phase, Power test
MEWOI168CMEWOI168.80.jpg0.00A~1000A (AC)

1mA,

Accuracy: 2% 

Φ68mm

suitable for current, harmonic, phase, Power test
MEWOI168BEMEWOI168BE-80.jpg

0.0A~2000A (DC),

0.0A~1000A(AC)

0.1mAΦ68mm

Power supply: 9VDC,

output:1mV/1A, 

Accuracy: 2%


suitable for AC/DC big current test

SELECTION GUIDE 2

Flexible Coil Current Sensor Probe For Terminals Such as Mulitimeter&Oscilloscope 

Click "Blue" marked Model No. to View the Spec

Model
Flexible CTRangeResolutionCoil lengthDiameterApplication
MEWOI200GMEWOI200G-80.jpgΦ100 mm

AC

10mA~10000A~more

10mA315mm (Can be customized)φ7.5mm(suitable for narrow and cable-intensive places)



Measure AC big current, high harmonic currents, complex Waveforms current,   inrush transient current.


Suitable for measuring the size of a large or irregularly shaped conductor current

MEWOI300GMEWOI300G-80.jpgΦ200 mm

AC

10mA~10000A~more

10mA630mm (Can be customized)φ7.5mm(suitable for narrow and cable-intensive places)
MEWOI400GMEWOI400G-80.jpgΦ300 mm

AC

10mA~10000A~more

10mA1000mm (Can be customized)φ7.5mm(suitable for narrow and cable-intensive places)

TECHNICAL SPECIFICATION

Function

Measurement of AC current, phase, power energy, power, power factor

Power supply

Zn-Mn dry battery 6F22 9VDC(external power is allowed)

Rated current

15mA

Test mode

Clamp CT, noncontact measurement

Clamp Size

Φ68mm

Range

DC 0.0~2000A; AC 0.0~1000A

Resolution

0.1A AC/DC

Signal output

1mV/1A

Accuracy

±2.0%FS(50Hz/60Hz; 23±2, below 70%RH, keep the wire be in the center of clamp)

Phase Error

≤3°(AC50Hz/60Hz; 23±2)

Zero clearing

Press ZERO key can clear the data, eliminate the effect of geomagnetic field to the measure of AC current
Output connectionStandard connection: Red wire-positive output; Yellow wire-negative output.
Output Wire Length2m

Measured Wire Position

Approximately in the geometric center of the clamp, the errors for deviating the center of the clamp increase 1.5%rdg.

Frequency

AC 45Hz~400Hz

Voltage of circuit

Circuit with the voltage below AC 600V

Voltage of battery

When the voltage of battery is below 7.2V, the LED will be lighted when the voltage is low, indicate to replace the battery.

Dimension

224mm×115mm×43mm

Weight

515g

Working Environment

-15~45;80%rh below

Storage Environment

-10~60;70%rh below

Insulation Strength

AC 3700V/rms. (between core and shell)

Safety Rules

IEC1010-1,IEC1010-2-032,Pollution degree 2,CAT Ⅲ(600V)

Accessory

Sensor:1pc; battery(6F22 9V):1pc

Sensor:1pc; battery(6F22 9V):1pc

Telephone
E-mail
After Sales