INTRODUCTION
Click to download: MEWOI7900 User Manual
Click to download: MEWOI7900 Color Page
The MEWOI7900 Rogowski current clamp is designed for the test of big current and leakage current. It is widely used in the fields of electric power, communication, meteorology, railway, oil field, construction, measurement, scientific research and teaching units, industrial and mining enterprises and so on. The cable is especially suitable for intensive places, the current industrial environment such as the wall- subway transformer core current test, thick wire cable test, relay protection, silicon controlled rectifier, inverter, semiconductor switch, power electronic conversion equipment, arc welding and other serious distortion of the signal of the test. Flexible current clamp, namely Rogowski Coil (Rockwell coil), is a circular coil uniformly wound on non-ferromagnetic materials, no hysteresis effect, almost zero phase error, no magnetic saturation, high linearity, strong anti-interference ability. The output signal is the differential of current to time. By integrating the output voltage signal, the input current can be truly restored, and the current range can be from mA to 10000A. Flexible coil current clamp part without any bare metal conductor, non-contact measurement, safe and fast; the small size and light weight, beautiful appearance, soft and flexible, suitable for narrow environment and cable intensive sites; high accuracy, strong reliability, frequency bandwidth, users can be customized according to the length of the coil. The instrument also has the functions of peak retention, data retention, data storage and so on. It is a necessary tool for electrical safety inspection. |
TECHNICAL SPECIFICATION
Function | Big AC current, leakage current measurement |
Power | Zn-Mn dry battery,6F22,9V |
Test Mode | Flexible CT: the output signal is the differential of the current to the time. By integrating the output voltage signal, the input current can be restored. |
Coil Diameter | φ200mm |
Range | AC 0.00A ~ 9999A |
Resolution | AC 10mA |
Accuracy | 2% + 3dgt (the tested wire is in the central position of the flexible coil, 23℃±2℃) |
Coil length | 628mm |
Coil thickness | Coils of thickness (7.5mm) (very suitable for a narrow environment and a dense line of rows, etc.) |
Frequency | 50Hz/60Hz (automatic recognition) |
Display Mode | Four digits LCD display |
Dimension | Width × Height× Thickness:190mm×370mm×40mm |
LCD Dimension | 35mm×21.5mm;display domain:32mm×15mm |
Backlight | Support |
Weight | 200g |
Electric field interference | has no hysteresis effect and strong anti-interference ability |
Position Error | The position error of the measured wire should be at the center of the flexible coil as far as possible, not close to the opening port, and the test error at the opening port is about twice or more. |
Sampling Rate | 2times/sec |
Data Memory | 99sets, display "FULL" symbol indicates that the storage is full |
Peak Hold | Push HOLD without release, shows the peak value symbol |
Reading Hold | DHindicating the reading is hold |
Voltage Range | AC600V |
Out of Range | OL indicating the current is out of range |
Battery Voltage | Indicating the battery voltage is lower then 7.2V.Then the battery have to be changed |
Rated Current | About 8mA |
Temperature and Humidity | Working: 0℃~40℃,below 80%rh, Storage: -10℃~60℃,below 70%rh |
Insulation resistance | 100M Omega or larger, 1000V |
Applicable Safety Rules | IEC1010-1、IEC1010-2-032、pollution grade 2、CAT VI (1000V) IEC61326 (EMC standard) |
APPLICATION